Lossnay Structure


The Lossnay core is a crossflow plate-fin total heat exchanger composed of partition plates and spacer plates made of special processed paper. As the air-supply and -exhausting passages are completely separated by partition plates, fresh air is constantly introduced with no mixing of fresh and stale air.

Principle of Heat Exchange


  • Temperature (sensible heat) exchange

From the warmer to the cooler side, heat is conducted and passes through the partition plates.

  • Humidity (latent heat) exchange

Due to the difference in the water-vapor partial pressure, water vapor is transferred from the high-humidity side to the low-humidity side through the partition plates.

Heat exchange and save energy


The air conditioner needs not be so powerful which help saving energy. 

Excellent sound insulation


The structure of the Lossnay core transmits little air vibration and absorbs sound. Lossnay is approved as noise control equipment for houses in noisy areas near airports, and is also used in areas near railroads and highways.

High durability


Specifications

Model LGH-15RVX3 LGH-25RVX3 LGH-35RVX3 LGH-50RVX3 LGH-65RVX3 LGH-80RVX3 LGH-100RVX3 LGH-160RVX3 LGH-200RVX3
Air volume (E.Low-Hi) m³/h 38/75/113/150 63/125/188/250 88/175/263/350 125/250/375/500 163/325/488/650 200/400/600/800 250/500/750/1000 375/750/1125/1500 500/1000/1500/2000
External static pressure (E.Low-Hi) Pa 8/30/68/120 8/30/68/120 10/40/90/160 10/38/85/150 10/38/85/150 11/43/96/170 12/48/107/190 11/44/98/175 11/43/96/170
Power consumption (E.Low-Hi) W 10/15/30/55 11/21/42/75 15/29/61/120 15/34/81/185 20/51/120/245 23/64/160/343 27/83/210/438 38/123/311/670 57/163/416/855
Noise level (E.Low-Hi) dB(A) 17/18/22/27 17/19.5/25/30.5 17/19/24.5/30.5 17/21/27/35 17.5/24/31.5/37.5 18/25/33.5/39 18.5/27/35/40 18/24/32/39 18/27.5/36/41.5
Temperature exchange efficiency (E.Low-Hi) % 78/73.5/70.5/65.5 (Cooling)81.5/78/75.5/73.5 (Heating) 85/79/76.5/70.5 (Cooling)88/81/78.5/75.5 (Heating) 79/74/71/66.5 (Cooling)82/79/77/75 (Heating) 73/71/67/63.5 (Cooling)75/73.5/71.5/70.5 (Heating) 80/74.5/70/65 (Cooling)82/78.5/75/72.5 (Heating) 78/75.5/70/65 (Cooling)80/78/76.5/75 (Heating) 82.5/77/72/67.5 (Cooling)83.5/79.5/77/75.5 (Heating) 78/75.5/70/65 (Cooling)80/78/76.5/75 (Heating) 82.5/76/71.5/66.5 (Cooling)83.5/79.5/77.5/76.5 (Heating)
Enthalpy exchange efficiency (E.Low-Hi) % 73/66/62/58 (Cooling)80.5/76.5/73.5/70.5 (Heating) 75/68/63.5/59 (Cooling)84/75.5/72/69 (Heating) 74.5/68.5/64.5/60 (Cooling)80/77.5/74.5/72 (Heating) 68/63/58/53.5 (Cooling)73/72/69.5/68.5 (Heating) 80/74.5/70/65 (Cooling)80/76.5/72/69.5 (Heating) 78/75.5/70/65 (Cooling)73.5/70.5/65/62 (Heating) 82.5/77/72/67.5 (Cooling)75.5/68.5/63/60.5 (Heating) 78/75.5/70/65 (Cooling)73.5/70.5/65/62 (Heating) 82.5/76/71.5/66.5 (Cooling)76/67.5/64/60.5 (Heating)
Duct size mm 100 150 150 200 200 250 250 258 258
Dimension (HxWxD) mm 289x610x888 289x735x908 331x874x1016 331x1016x1046 404x954x1066 404x1004x1302 404x1231x1302 808x1004x1267 808x1231x1267
Weight kg 20 22 30 33 41 47 53 96 108
Power supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50 220-240/1/50
Model LGH-15RVX3 LGH-25RVX3 LGH-35RVX3
Air volume (E.Low-Hi) m³/h 38/75/113/150 63/125/188/250 88/175/263/350
External static pressure (E.Low-Hi) Pa 8/30/68/120 8/30/68/120 10/40/90/160
Power consumption (E.Low-Hi) W 10/15/30/55 11/21/42/75 15/29/61/120
Noise level (E.Low-Hi) dB(A) 17/18/22/27 17/19.5/25/30.5 17/19/24.5/30.5
Temperature exchange efficiency (E.Low-Hi) % 78/73.5/70.5/65.5 (Cooling)81.5/78/75.5/73.5 (Heating) 85/79/76.5/70.5 (Cooling)88/81/78.5/75.5 (Heating) 79/74/71/66.5 (Cooling)82/79/77/75 (Heating)
Enthalpy exchange efficiency (E.Low-Hi) % 73/66/62/58 (Cooling)80.5/76.5/73.5/70.5 (Heating) 75/68/63.5/59 (Cooling)84/75.5/72/69 (Heating) 74.5/68.5/64.5/60 (Cooling)80/77.5/74.5/72 (Heating)
Duct size mm 100 150 150
Dimension (HxWxD) mm 289x610x888 289x735x908 331x874x1016
Weight kg 20 22 30
Power supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50
Model LGH-50RVX3 LGH-65RVX3 LGH-80RVX3
Air volume (E.Low-Hi) m³/h 125/250/375/500 163/325/488/650 200/400/600/800
External static pressure (E.Low-Hi) Pa 10/38/85/150 10/38/85/150 11/43/96/170
Power consumption (E.Low-Hi) W 15/34/81/185 20/51/120/245 23/64/160/343
Noise level (E.Low-Hi) dB(A) 17/21/27/35 17.5/24/31.5/37.5 18/25/33.5/39
Temperature exchange efficiency (E.Low-Hi) % 73/71/67/63.5 (Cooling)75/73.5/71.5/70.5 (Heating) 80/74.5/70/65 (Cooling)82/78.5/75/72.5 (Heating) 78/75.5/70/65 (Cooling)80/78/76.5/75 (Heating)
Enthalpy exchange efficiency (E.Low-Hi) % 68/63/58/53.5 (Cooling)73/72/69.5/68.5 (Heating) 80/74.5/70/65 (Cooling)80/76.5/72/69.5 (Heating) 78/75.5/70/65 (Cooling)73.5/70.5/65/62 (Heating)
Duct size mm 200 200 250
Dimension (HxWxD) mm 331x1016x1046 404x954x1066 404x1004x1302
Weight kg 33 41 47
Power supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50
Model LGH-100RVX3 LGH-160RVX3 LGH-200RVX3
Air volume (E.Low-Hi) m³/h 250/500/750/1000 375/750/1125/1500 500/1000/1500/2000
External static pressure (E.Low-Hi) Pa 12/48/107/190 11/44/98/175 11/43/96/170
Power consumption (E.Low-Hi) W 27/83/210/438 38/123/311/670 57/163/416/855
Noise level (E.Low-Hi) dB(A) 18.5/27/35/40 18/24/32/39 18/27.5/36/41.5
Temperature exchange efficiency (E.Low-Hi) % 82.5/77/72/67.5 (Cooling)83.5/79.5/77/75.5 (Heating) 78/75.5/70/65 (Cooling)80/78/76.5/75 (Heating) 82.5/76/71.5/66.5 (Cooling)83.5/79.5/77.5/76.5 (Heating)
Enthalpy exchange efficiency (E.Low-Hi) % 82.5/77/72/67.5 (Cooling)75.5/68.5/63/60.5 (Heating) 78/75.5/70/65 (Cooling)73.5/70.5/65/62 (Heating) 82.5/76/71.5/66.5 (Cooling)76/67.5/64/60.5 (Heating)
Duct size mm 250 258 258
Dimension (HxWxD) mm 404x1231x1302 808x1004x1267 808x1231x1267
Weight kg 53 96 108
Power supply V/Ph/Hz 220-240/1/50 220-240/1/50 220-240/1/50
Remarks